J3

5 digit configurable display colour indicator

- Panel mount indicator 96 x 48 mm
- 1 Universal input
- 1 Auxiliary high level input(Optional)
- 1 retransmission output(optional)
- Display of IN1, IN or CIN inclusive of
value, peak and valley and hold value
- RS 485 port with ModBus RTU Protocols (optional)
- 1 display, 5 digits, h: 15.5 mm,
configurable green or red colour

Process inputs:

1 Main Input IN1

- Thermocouples: L, J, T, K, S, R, B, N, E, Ni-NiMo, W3, W5
- RTD: Pt100
- Voltage (mV):0/10...50 mV
- Current (mA): 0/4...20 mA (with 2.5 Ω shunt resistor)
- Custom linearisation and IR probes (J.K type)
Accuracy : 0.25% ±1 digit (probes) or 0.1% ±1 digit (mA or mV)

Auxiliary input IN2 (Optional)

- Voltage (V):  0/1...5 V, 0...10V
- Current (mA): 0/4...20 mA
Accuracy : 0.25% ±1 digit (probes) or 0.1% ±1 digit (mA or mV)
Resolution: 16 Bit

3 digital inputs

- NPN
- TTL
- Free Voltage

Keyboard

Mechanical:
3 multifunction keys + 1 dedicated for alarm acknowledge

Process outputs

1 High level analogue output:

- Current (mA): 0/4...20 mA

Up to 4 Optional outputs:

OUT1
- RELAY SPDT, 2A/250Vac
OUT2
- RELAY SPST-NO, 2A (250VAC)
OUT3
- RELAY SPST-NO, 2A (250VAC)
OUT4
- RELAY SPST-NO, 2A (250VAC)
- SSR Drive 0...5Vdc, ±20%, 30 mA Max

Power supply:

- 24VDC/VAC
- 100… 240 Vac (50/60 Hz)
Transmitter power supply: 24 Vdc ±20%, 30 mA Max

Functions

Calculated value (CIN) Selectable between

- IN1 or IN2
- IN1 + IN2
- IN1 – IN2
- IN1 * IN2
- IN1/IN2
- (IN1 + IN2)/2 (average)
- MAX (IN1, IN2) (maximum value)
- Min (IN1, IN2)  (minimum value)
Display indication of :
- Main input IN1
- Auxiliary input IN2
- Calculated Value CIN
- Peak and Valley indication
- Hold and temporized indication

Alarms

- Up to 4 configurable alarms
- ISA-A Acknowledge function

Communication and programming:

Interfaces

- RS 485 port with ModBus RTU and J-bus (slave) protocols (optional)

Programming/configuration tools:

- Code selection
- Easy to use front interface for configuration
- Configuration software available for PC

Installation

Mounting method: panel mount
Case dimensions: 96 x 48 mm, depth 110 mm (1/8 DIN)

Connections

Signals connection
36 poles 5.5 mm² screw terminals block
Protection factor : IP 65 front protection

Display and indicators

1 display, 5 digits, h: 15.5 mm, configurable green or red colour
4 Alarm and 3 DI LED indicators

Connectable to:

- Any controller from Ascon Tecnologic range with the appropriate I/Os
- SCADA for monitoring, traceability and remote management
- DX and DY gateways for remote monitoring

UL Listed

File no. E176452
Ref. UL 504