1286

Description

Instantaneous relay 1, 2 or 3 CO contacts.

Connection with Faston double clips of 2.8 x 0.8 mm

Detailed table of coil resistance date is available in the technical support pages of this site or can be sent upon request.

Dimensions

Connection

Technical features

Function instantaneous
Presentation under cover
Connection on Faston double clips of 2.8 x 0.8 mm
Number of mechanical operations 10.000.000
Operating temperature - 10 to + 40°C
Storage temperature - 20°C to + 85°C
Climatic protection reinforced climatic protection
Shock voltage 15 g - 11 ms
Dielectric strength 2 KV-50 Hz-1 min at 40°C and 70% HR
Insulation resistance > 1.000 MOhms (new relay)
Weight 70 g.

Coil data

  Direct current Alternative current
Min. nominal voltage DC 6 V 6 V
Min. nominal voltage AC 220 V 400 V
Operating range -20/+10% of nominal voltage
Power requirement 2,2W 4,5 VA 3 VA

Contacts

Number of contacts 1, 2 or 3
Max. load current 10 A per contact
Low power switching 40 mA min for 6 V
Short-circuit load 250 A / 30 ms
Response time (bounce time not included) DC < 20 ms - AC < 25 ms
Bounce time < 7 ms

Contacts rating

DIRECT CURRENT
resistive load inductive load L/R = 20 ms
   
ALTERNATIVE CURRENT
resistive load inductive load cos phi = 0.7
   

Versions

Relay 1286 can be mounted on metal sheet (by plastic support + 2 M4 screws or by M4x8 bolt + positioning part) or on symetrical or dissymetrical DIN tracks with specific adaptators to be mentioned on your order.