Description
Instantaneous relay 1, 2 or 3 CO contacts.
Connection with Faston double clips of 2.8 x 0.8 mm
Detailed table of coil resistance date is available in the technical support pages of this site or can be sent upon request.
Dimensions
Connection
Technical features
| Function | instantaneous |
| Presentation | under cover |
| Connection | on Faston double clips of 2.8 x 0.8 mm |
| Number of mechanical operations | 10.000.000 |
| Operating temperature | - 10 to + 40°C |
| Storage temperature | - 20°C to + 85°C |
| Climatic protection | reinforced climatic protection |
| Shock voltage | 15 g - 11 ms |
| Dielectric strength | 2 KV-50 Hz-1 min at 40°C and 70% HR |
| Insulation resistance | > 1.000 MOhms (new relay) |
| Weight | 70 g. |
Coil data
| Direct current | Alternative current | ||
| Min. nominal voltage DC | 6 V | 6 V | |
| Min. nominal voltage AC | 220 V | 400 V | |
| Operating range | -20/+10% of nominal voltage | ||
| Power requirement | 2,2W | 4,5 VA | 3 VA |
Contacts
| Number of contacts | 1, 2 or 3 |
| Max. load current | 10 A per contact |
| Low power switching | 40 mA min for 6 V |
| Short-circuit load | 250 A / 30 ms |
| Response time (bounce time not included) | DC < 20 ms - AC < 25 ms |
| Bounce time | < 7 ms |
Contacts rating
| DIRECT CURRENT | ||||||
|
||||||
| ALTERNATIVE CURRENT | ||||||
|
||||||
Versions
Relay 1286 can be mounted on metal sheet (by plastic support + 2 M4 screws or by M4x8 bolt + positioning part) or on symetrical or dissymetrical DIN tracks with specific adaptators to be mentioned on your order.