Indicator, 1 input, 4 outputs and RS485 port
- Panel Mount, 78 x 35 mm format
- One programmable input
- Up to 4 outputs
- Built-in indipendent timer
- Counter for worked hours
- TTL or RS485 communication ports
- One 4 digit display line.
Process inputs:
1 temperature probe input
- Thermocouples: J, K, R, S,T
- PTC KTY81-121 (990 Ω @ 25 °C)
- NTC 103AT-2 (10KΩ @ 25 °C)
- RTD : PT100 IEC
- Voltage(V): 0..1 V, 0/1...5 V , 0/2...10 V
- Voltage(mV): 0...50 mV, 0...60 mV, 12 ...60 mV
- Current(mA): 0/4...20 mA
Overall accuracy: ± (0,5 % span ± 1 digit @25 °C), Tc S: ± (1 % span ± 1 digit @ 25 °C)
2 digital inputs:
- Free Voltage
Keyboard
Mechanical:4 keys for parameter changes
Process outputs:
Up to 4 Digital outputs
OUT1
-RELAY SPDT,8A
-SSR Drive
OUT2
-RELAY SPDT,8A
-SSR Drive
OUT3
-RELAY SPST-NO,5A
-SSR Drive
OUT4
-RELAY SPST-NO,5A
-SSR Drive
Power supply:
- 12 V AC/DC
- 24 Vac or 24Vdc
- 100… 240 Vac
Transmitter Power Supply: 10 V DC (+ 10%), 20 mA max.
Functions
- Indication only
- Independent timer with 4 functioning modes (optional)
- Counter for days and hours worked with programmable threshold for programmed maintenance
Alarms
Up to 3 configurable alarms + loop break alarm
Communication and programming:
Interfaces
Communication on TTL port to:
-Universal programming key
-Remote display
RS 485 port with ModBus RTU and J-bus (slave) protocols (optional and alternative to TTL)
Programming / Configuration tools
Configurable parameter level "Promotion"
Configuration software available for PC
Installation
Mounting method: Panel Mount
Controller Dimensions: 78 x 35 mm, depth 75.5 mm
Connections:
Communication port connection: 3 Pole TTL Port
Signals Connection: 24 poles 2,5 mm² screw terminals
Front protection: IP 65 (with gasket)
according to EN 60070-1 for indoor use
Display and Indicators:
1 Display line, 4 Digit, h 12 mm, red color
3 LED Bargraph
Connectable to:
- Programming key A01 for PC connection, Backup and other functions
- SCADA for Monitoring, traceability and remote management
- DX and DY Gateways for remote monitoring
File no. E362268
Ref. UL 61010-1 CSA 61010-1
(power supply 12 VAC/DC only)