CAT
Description
Fixed timing relay (1 s) with capacitor - 2 CO contacts - 8 A.
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB2/CA, ERC2/CA or ERDL2/CA
Dimensions
Connection
Operation principle
Functions :
* ET - timed on voltage application
* MT - timed on voltage lack
Timing : 1 s
operation accuracy : +/- 50%
Fidelity at nominal voltage at 20°C : 20%
Technical features
Function | timer (ET, MT) |
Presentation | under cover |
Connection | on front or rear wiring socket |
Number of mechanical operations | 35.000.000 |
Operating temperature | - 5°C to + 40°C |
Storage temperature | - 40°C to + 70°C |
Climatic protection | optional reinforced climatic protection |
Shock voltage | 5 KV (wave 1,2/50 µs) |
Dielectric strength | 2200 V eff |
Insulation resistance | NFC 45-202 : C380 - VDE0110 : C500 |
Weight | 200 g. |
Protection level | IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks | severity 50 A (NFC 20-608 & CEI 68-2-27) |
Resistance to vibrations | 0,35 mm / 10-55 Hz |
Operate time | min power supply duration : 500 ms |
Release time | recycling time : 250 ms |
Coil data
Direct current | Alternative current | ||
Min. nominal voltage DC | 24 V | 24 V | |
Min. nominal voltage AC | 220 V | 380 V - 50/60 Hz (380 V only for ET function) | |
Operating range | -20/+10% of nominal voltage | ||
Power requirement | 0,5 to 1,8 W |
Contacts
Number of contacts | 2 |
Max. load current | 8 A per contact |
Low power switching | 0,1 VA with min voltage 1 V or I min 1 mA |
Contacts rating
DIRECT CURRENT | ||||||
|
||||||
ALTERNATIVE CURRENT | ||||||
|
Versions
. CAT relay with reinforced climatic protection
. CAT relay with high contacts rating
Homologations & conformities :
* CEI 255-1-00
* NFC 45-250