GAP

Description

Impulse relay - 4 CO contacts - 3 A.

Pluggable on socket with possible withdrawal clasp. Pins at the standard pitch of 2.54 mm. Possibility of polarizatio by mounting a male withdrawal clasp on the relay and a female withdrawal clasp on the socket.

GAP relay is pluggable on the following sockets : EVB/GE,  9877, EVC/GE, 9876, ER/GE 2.8, or ER/GE.

Dimensions

Connection

Operation principle

Functions :

* ET : impulse on voltage application
* MT : impulse on voltage lack

Duration of impulse contact : 0,15 to 1 s
Interval between 2 operations : > 1 s

Technical features

Function impulse (ET - MT)
Presentation under cover
Connection on front or rear wiring socket
Number of mechanical operations 30.000.000
Operating temperature - 5°C to + 40°C
Storage temperature - 40°C to + 70°C
Climatic protection optional reinforced climatic protection
Dielectric strength 2000 V eff-50 Hz
Insulation resistance NFC 45-202 : C 250 V
Weight 60 g.
Protection level IP40 (according to NFC 20-010)
Resistance to mechanical shocks severity 50 A (NFC 20-608)
Resistance to vibrations frequency range : 10-55 Hz (NFC20-616)

Coil data

  Direct current Alternative current
Min. nominal voltage DC 24 V 24 V
Min. nominal voltage AC 230 V 230 V
Operating range -20/+10% of nominal voltage
Power requirement ET : 2 W - MT : 0,5 W    

Contacts

Number of contacts 4
Max. load current 3 A
Low power switching 0,1 VA with min voltage 1 V and/or I min 1 mA
Response time (bounce time not included) < 14 ms

Contacts rating

DIRECT CURRENT
connection on DC
 
ALTERNATIVE CURRENT
connection on AC
 

Versions

. GAP relay with reinforced climatic protection
. GAP relay with specific voltages.

Homologations & conformities :

NFC 45-250
CEI 255.1.00