TLI40

Digital indicator

  • 1 temperature probe input:
    - Thermocouples: J, K, S, B, C, E, L, N, R, T
    - PTC KTY81-121 (990 Ω @ 25 °C)
    - NTC 103AT-2 (10KΩ @ 25 °C)
    - RTD : PT100 IEC
    - Voltage (V):  0/1...5 V, 0/2...10V
    - Voltage (mV): 0...50 mV, 0/12...60mV
    - Current (mA): 0/4...20 mA
    - Potentiometer: with value higher than 1 KΩ
    - IR probes (J.K type)
    Overall accuracy: ± 0,15 % fs
  • Sampling time: from 8 to 64 samples/ second for V,C or potentiometer signals
  • 1 digital input - Free Voltage
  • Keyboard: mechanical - 4 multifunction keys
  • Up to 4 outputs according to the configuration:
    OUT1:
    - Relay SPST-NO 5 A-AC1 (2 AAC3/ 250 VAC)
    - SSR servomotor drive  (14 VDC/7 mA)
    - Analogue output: 0/4 ..20 mA or 0/2 ..10 V
  • OUT2 to OUT 4
    - Relay SPST-NO 5 A-AC1 (2 AAC3/ 250 VAC)
    - SSR servomotor drive  (14 VDC/7 mA)
  • Power supply: 24 VAC/VDC or 100...240 VAC
  • Auxiliary power supply for external transmitters (optional):
    - 12 VDC/20 mA max
    - 2,5 VDC/2,5 mA max. for Potentiometers
  • Functions:
    - Acquisition and retransmission
    - Indication
  • Up to 4 configurable alarms with the following  type:
    - Probe errors
    - Temperature tresholds: (absolute or relative)
  • Communication and programming:
  • Communication on TTL port to:
    - Universal programming key
    - Remote display
    - RS 485 serial interface
    - RS 485 port(optional) with ModBus RTU and J-bus (slave) protocols
  • Programming/configuration tools:
  • - Easy to use front interface for configuration
    - Configuration software available for PC
  • Mounting method: panel mount
    Case dimensions: 48 x 48 mm, depth 98 mm (1/16 DIN )
  • Signals connection
    - 2.5 mm² screw terminals block
    - 2.5 mm² extractable screw terminals block (optional )
    - IP65 front frame protection, with gasket
  • Display and indicators: 1 display 4 digits, h 12 mm, red colour, 3 LED Bargraph
  • Connectable to:
    - Programming key A01 for PC connection, backup and other functions
    - Any controller from Ascon Tecnologic range with the appropriate I/Os
    - SCADA for monitoring, traceability and remote management
    - DX and DY gateways for remote monitoring

UL Recognition Canada USA