Description
Instantaneous relay - 4 CO contacts - 5 A..
Pluggable on following sockets : 9876, 9877, EVB/GE, EVC/GE, ER/GE 2,8 ou ER/GE.
Detailed table of coil resistance data is available in the technical support pages of this site or can be sent upon request.
Dimensions
Connection
Technical features
Function | Instantaneous |
Presentation | under cover |
Connection | on front or rear wiring socket |
Number of mechanical operations | 30.000.000 |
Operating temperature | min: +5 to +55??C - extr: -25 to +55??C (NFC45-250 |
Storage temperature | - 40??C to + 80??C (NFC 45-250) |
Climatic protection | reinforced climatic protection |
Shock voltage | 4 KV wave 1,2/50 ms (HN 45-S-25) |
Dielectric strength | 2200 KV Eff50 Hz. (coil/contacts), 2500 V Eff50 Hz |
Insulation resistance | > 200.000 MOhms (500 VDC new relay) |
Weight | 40 g. |
Protection level | IP40 |
Resistance to mechanical shocks | severity 50 A (NFC 20-608) |
Resistance to vibrations | frequency rance : 10-55 Hz (NFC 20-616) |
Coil data
Direct current | Alternative current | ||
Min. nominal voltage DC | 6 V | 6 V 50 Hz | |
Min. nominal voltage AC | 220 V | 230 V - 50 Hz | |
Operating range | Ic1:-20/+10% - Ib2:-15/+20% of nominal voltage | ||
Power requirement | 1,2 W | 2 VA (operate) | 1,6 VA (release) |
Contacts
Number of contacts | 4 |
Max. load current | Ic1: 3 A per contact / Ib2: 5 A per contact |
Low power switching | 0.1 VA with min. voltage 1 V and/or I min 1 mA |
Short-circuit load | 100 A / 30 ms |
Response time (bounce time not included) | DC < 11.5 ms - AC < 13 ms |
Contacts rating
DIRECT CURRENT | ||||
|
||||
ALTERNATIVE CURRENT | ||||
|
Versions
. 1804 relay frequency 60 Hz
. 1804 relay with specific voltages
. 1804 relay with internal protection (diode)