Description
Impulse relay - 4 CO contacts - 3 A.
Pluggable on socket with possible withdrawal clasp. Pins at the standard pitch of 2.54 mm. Possibility of polarizatio by mounting a male withdrawal clasp on the relay and a female withdrawal clasp on the socket.
GAP relay is pluggable on the following sockets : EVB/GE, 9877, EVC/GE, 9876, ER/GE 2.8, or ER/GE.
Dimensions
Connection
Operation principle
Functions :
* ET : impulse on voltage application
* MT : impulse on voltage lack
Duration of impulse contact : 0,15 to 1 s
Interval between 2 operations : > 1 s
Technical features
| Function | impulse (ET - MT) |
| Presentation | under cover |
| Connection | on front or rear wiring socket |
| Number of mechanical operations | 30.000.000 |
| Operating temperature | - 5°C to + 40°C |
| Storage temperature | - 40°C to + 70°C |
| Climatic protection | optional reinforced climatic protection |
| Dielectric strength | 2000 V eff-50 Hz |
| Insulation resistance | NFC 45-202 : C 250 V |
| Weight | 60 g. |
| Protection level | IP40 (according to NFC 20-010) |
| Resistance to mechanical shocks | severity 50 A (NFC 20-608) |
| Resistance to vibrations | frequency range : 10-55 Hz (NFC20-616) |
Coil data
| Direct current | Alternative current | ||
| Min. nominal voltage DC | 24 V | 24 V | |
| Min. nominal voltage AC | 230 V | 230 V | |
| Operating range | -20/+10% of nominal voltage | ||
| Power requirement | ET : 2 W - MT : 0,5 W | ||
Contacts
| Number of contacts | 4 |
| Max. load current | 3 A |
| Low power switching | 0,1 VA with min voltage 1 V and/or I min 1 mA |
| Response time (bounce time not included) | < 14 ms |
Contacts rating
| DIRECT CURRENT | ||||
|
||||
| ALTERNATIVE CURRENT | ||||
|
||||
Versions
. GAP relay with reinforced climatic protection
. GAP relay with specific voltages.
Homologations & conformities :
NFC 45-250
CEI 255.1.00