Controller for refrigerating units, 3 inputs and 4 outputs
- Power supply and control unit 92 x 92 mm,depth 27.8 mm
- Front protection degree IP40 with gasket
- 1 red or blue display 2 digits, h 31 mm (P03S)or 54 mm (P05S)
- Power supply: 100 ... 240 VAC ± 10% (50/60Hz)
- Power consumption: approximately 4 VA
- Inputs:
B05: 3 inputs for temperature probes PTC (KTY81-121, 990 ohms @ 25°C) or NTC (103AT-2,10 Kohm @ 25°C) or Pt1000 (1000 ohms @0°C) 2 of which may be digital for voltage free contacts.
P03S/P05S: 1 digital input for free voltage contacts - Outputs: up to 4 relay outputs:
- OUT1: SPST-NO-16A-250V 1HP - EN 61810:16 (9) - EN 60730: 6 (4) - UL 60730: 6 A Res.,30 LRA, FLA 5
- OUT2: SPST-8A-1 / 2HP 250V - EN 61810: 8(3) - EN 60730: 4 (4) - UL 60730: 4 A Res., 24LRA, FLA 4
- OUT3: SPST-5A-250V - EN 61810: 5 (1) - EN60730: 1 (1) A - UL 60730: 1 A Res.
- OUT4: SPST-5A-250V -EN 61810: 5 (1) - EN60730: 1 (1) A - UL 60730: 1 A Res.
- Common power supply (pin 1): 12 A Max.
- B05 connections (power and outputs): 6-pinAMP MATE-N-LOK .250 " removable connector
- Connection P03S/P05S - B05: 3 m max through cable with mini removable connectors
- Measurement range: PTC: -50 ... 99°C / -58 ...99°F; NTC: -50 ... 99°C / -58 ... 99°F; Pt1000:-99 ... 99°C / -99 ... 99°F
- Display resolution: 1° or 0.1° (in -9.9 ... 9.9°)
- Overall accuracy: ± 0.5% fs + 1 digit
- ON / OFF control
- Defrost control: interval or temperature modewith electric heating, hot gas/reverse cycle, by stopping compressor
Cable to connect panel and control unit:
0.8 m = CALIND080--
1.2 m = CALIND120--
3.3 m = CALIND330--
File no. E206847
Ref. UL/CSA 60730-1-2-9