Thyristor power controller up to 1450 kVA
- Dimensions according to power size
- Control signal:
Voltage, Current or potentiometer
- Output voltage (Vac): up to 600
- Output current (A): up to 1500
- Operating Modes:
* Full wave
* Half wave
* Phase angle VAR
- Communication Interfaces (optional):
* DeviceNet
* Modbus RTU
* PROFIBUS DPV1
* Ethernet
* CANopen
- Diagnostic LED
Control Input:
- Voltage (V): 0/1...5V (Ri 44 kΩ),
0/2...10V (Ri 88 kΩ)
- Current (mA): 0/4...20 mA(Ri 250 Ω)
- Potentiometer: 5...10 kΩ
Process outputs
- Voltage Rating (Vac):
230 (1A), 400, 500, 600
- Nominal Current (A):
16, 30, 45, 60, 100, 130, 170, 280, 350, 495,
650, 1000, 1400, 1500
- Load Type:
* Resistive
* Transformer
* High Rh/Rc temperature coefficient (6:1)
Functions
Operating Modes:
- Full wave switch operation TAKT
- Half wave switch mode
without continous component QUICK TAKT
(QTM only on A1)
- Phase angle VAR (not 2A)
Communication and programming:
Interfaces
(Optional)
- DeviceNet
- Modbus RTU
- PROFIBUS DPV1
- Ethernet
- CANopen
Installation
Case dimensions:
(Lenght x height x depth)
From 45 x 136 x 129 to 583 x 685 x 516 mm
according to power size
Power circuit wiring:
- Single phase (1A)
- Symmetrical loads in three phase
economy circuit operation (2A)
- Three phase operation (3A)
Operating temperature:
170 A: -10... +45°C (natural ventilation)
From 280 A: -10... +35°C (forced cooling)
Display and indicators
Diagnostic and level LED
Connectable to:
- Any controller from Ascon Tecnologic range
with the appropriate I/Os
Certifications : CE, UL
Integrated protection against contact
USB interface