Description
Instantaneous relay with rapid memory.
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB2/CA, ERC2/CA or ERDL2/CA.
Dimensions
Operation principle
This relay is a rapid memory which acts when it receives an impulse with duration > 0.5 ms (terminal 14). This information is re-sent (tipping of the two CO contacts) when validated by action on terminal 13 (validation). This information is directly re-sent il terminals 13 and 15 are linked. Return to rest state is made by cutting-off terminal 15 (reset).
See the operation diagram hereafter
Technical features
Function | instantaneous |
Presentation | under cover |
Connection | on front or rear wiring socket |
Number of mechanical operations | 35.000.000 |
Operating temperature | - 5°C to + 40°C |
Storage temperature | - 40°C to + 70°C |
Climatic protection | optional reinforced climatic protection |
Shock voltage | 3 KV (wave 1,2/50 µs) |
Dielectric strength | 2200 V eff |
Weight | 200 g. |
Protection level | IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks | severity 50 A (according to NFC 20-608) |
Resistance to vibrations | 0,35 mm / 10-55 Hz (according to NFC 20-616) |
Coil data
Direct current | Alternative current | ||
Min. nominal voltage DC | 12 V | ||
Min. nominal voltage AC | 220 V | ||
Operating range | -20/+10% of nominal voltage | ||
Power requirement | 4 W permanently - 0,5 W control impulse |
Contacts
Number of contacts | 2 |
Max. load current | 8 A per contact |
Low power switching | 0,1 VA with min voltage 1 V and/or I min 1 mA |
Contacts rating
DIRECT CURRENT | ||||||
|
||||||
ALTERNATIVE CURRENT | ||||||
|
Operation diagram
see detailed operation diagram here above
Versions
. CAQ relay with reinforced climatic protection
. CAQP relay with control by positive polarity
. CAQN relay with control by negative polarity
. CAQ relay with impulse < 0,5 ms