CACTA-Z04AA
Description
Electronic timer relay adjustable from 0.2 to 300 Sec in three ranges - 2 timed contacts / 2 instantaneous contacts - 3 A.
To substitute the obsolete BC relay
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB1/CA, ERC1/CA, ERDL1/CA.
Dimensions
Connection
Operation principle
Functions :
* ET : timed on voltage application
* MT : timed on voltage lack
Timing (3 ranges) adjustable by potentiometer on front face :
* 0,2 to 3 s
* 2 to 30 s
* 20 to 300 s
operation accuracy : +/- 5%
Fidelity : 2% at 20°C
Recycling time >= 50 ms
minimum supply time (MT function) : 500 ms
Technical features
Function | timer (ET, MT) |
Presentation | under cover |
Connection | on front or rear wiring socket |
Number of mechanical operations | 30.000.000 |
Operating temperature | - 5°C to + 40°C |
Storage temperature | - 40°C to + 70°C |
Shock voltage | 3 KV (wave 1,2/50 µs) |
Dielectric strength | 1000 to 2200 V eff |
Weight | 300 g. |
Protection level | IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks | severity 50 A (NFC 20-608 & CEI 68-2-6) |
Resistance to vibrations | 0,35 mm / 10-55 Hz |
Coil data
Direct current | Alternative current | ||
Min. nominal voltage DC | 24 V | 24 V | |
Min. nominal voltage AC | 230 V | 230 V | |
Operating range | -20/+10% of nominal voltage | ||
Power requirement | 3 W |
Contacts
Number of contacts | 2 |
Max. load current | 3 A per contact |
Low power switching | 0,1 VA with min. voltage 1 V and/or I min 1 mA |
Contacts rating
DIRECT CURRENT | ||||
|
||||
ALTERNATIVE CURRENT | ||||
|
Versions
Homologations & conformities :
* CEI 255-1-00
* NFC 45-250