1831-1832

1831-1832

Description

Timer module, based on an electronic technology grouping components ensuring timing and counting functions and controlling an output relay type GE or 1804.

Timer module on opening (O) : 1832
Timer module on closing  (F) : 1831

Pluggable on following sockets : 9876, 9877, EVB/GE, EVC/GE, ER/GE 2,8 ou ER/GE.

Dimensions

Connection

Operation principle

Timer under plastic cover grouped with an intantaneous relay type GE / GFN or 1804 - Qualified EDF HN45S30 :

Timing adjustable in 3 ranges from 0.6 to 600 sec.
Ranges selection by strapp on the basis.
Time selection by potentiometer on front face.

See operation diagram hereafter.

Technical features

Function timer
Presentation under cover
Connection on front or rear wiring socket or on PCB
Operating temperature - 10 to + 55°C
Storage temperature - 40°C to + 80°C
Climatic protection reinforced climatic protection
Protection level IP50

Coil data

  Direct current Alternative current
Min. nominal voltage DC 24 V 24 V
Min. nominal voltage AC 125 V 125 V
Power requirement 1,8 W    