GAT

GAT

Description

Electronic adjustable timer relay - Timing fro 0.2 to 1500 s in 4 ranges - 3 contacts (GAT-MT) or 4 contacts (GAT-ET) - 3 A.

Pins at the standard pitch of  2.54 mm.
 
GAT relay is pluggable on the following sockets : EVB/GE, 9877, EVC/GE, 9876, ER/GE 2.8, or ER/GE.

Dimensions

Connection

Operation principle

Functions :

ET : timed on voltage application
MT : timed on voltage lack

Short timing :

* range A : 0.2 to 2.5 s
* range B : 2 to 20 s

Long timing :

* range A : 15 to 180 s
* range B : 120 to 1500 s

- Operation accuracy : + or - 10%
- Fidelity : 2% in DC
- Recyclig time : 20 ms
- Minimum power supply duration in MT function : 20 ms in DC - 50 ms in AC

Relay equipped in its standard version with a timing range selector on front face and a red LED indicating the status of the timed contacts.

Technical features

Function timer (ET-MT)
Presentation under cover
Connection on front or rear wiring socket
Number of mechanical operations 30.000.000
Operating temperature - 5°C to + 40°C
Storage temperature - 40°C to + 70°C
Climatic protection optional reinforced climatic protection
Dielectric strength 2000 V eff-50 Hz
Insulation resistance > 200.000 MOhms
Weight 70 g.
Protection level IP30 (according to NFC 20-010)
Resistance to mechanical shocks severityé 50 A (NFC 20-608)
Resistance to vibrations frequency range : 10-55 Hz (NFC20-616)

Coil data

  Direct current Alternative current
Min. nominal voltage DC 24 V 24 V
Min. nominal voltage AC 220 V 230 V
Operating range -20/+10% of nominal voltage
Power requirement 2 W (3,5 W in 220 VDC)    

Contacts

Number of contacts 3/4
Max. load current 3 A
Low power switching 0,1 VA with min voltage 1 V and/or I min 1 mA

Contacts rating

DIRECT CURRENT
connection on DC
 
ALTERNATIVE CURRENT
connection on AC
 

Versions

. GAT relay with timing up to 3600 s

Homologations & conformities :

NFC 45-250
CEI 255.1.00