79R2

79R2

Weight : 140 g.

Power supply : 6 to 48 VDC

Description

VOLTAGE CUT-OFF SAFETY HOLD MAGNET SOLENOID

CURRENT : DIRECT  -  OPERATION : HOLDING

Holding of a system in a determined position and guaranteed in accordance with the NFS 61-937 standard for security operated system.

Detachment obtained :

1. by cutting off the voltage supply,
2. manually, by pulling a higher force than the holding force.

The return to the "hold" position is obtained by bringing back the counter-plate in the initial position.

Dimensions

• Direct current

79R2 - Front view   79R2 - Back view
   

Technical features

Hold force > or = 12 daN
Min. effort of detachment 1,5 daN at 0 V
Standard voltages (Nom. Voltage ± 10%)
(others voltages on demand)
24 VDC - 48 VDC
Nominal power at 20°C 1,5 W
Connection On wires length 200 mm